January 10, 2019

Specifications

Brochure

Specifications

Hot Temperature 60°C – 75°C
Cold Temperature 15°C – 24°C – User definable
Working Pressure 500 kPa (PRV supplied)
Expansion Control Valve 550 kPa x 2 (supplied)
Pressure Temp Relief Valve 850 kPa x 2 (supplied)
Cylinder Material Vitreous Enamel Lined Steel – Y Class
Anode 2 x Aluminium per Cylinder
Electric Element 3 x 3600W or 3 x 4800W per Cylinder

           Recovery Rates (Litres per Hour)

HP Model Cold Hot
10 kW system 176 LPH 176 LPH
15 kW system 266 LPH 266 LPH
20 kW system 352 LPH 352 LPH
30 kW system 533 LPH 533 LPH

            Maximum Flow Rate Combined (Litres per Minute)/Pressure loss (kPa)

Valve Model
25mm valve 80/145
32mm valve 180/160
40mm valve 280/195
50mm valve 380/200